Raised Access Floor Barrier
For voids beneath raised access floors
PRODUCT
AIM Raised Access Floor Barrier prevents the passage of flame and smoke through the under floor cavity, for at least the period of fire rating specified. AIM Raised Access Floor Barrier is made from high density Rockwool stone wool slab, faced with Class 0 impervious foil facing on both sides. It is available cut to size or in slabs suitable for cutting on site.
APPLICATIONS
Raised Access Floor Barriers are required for four
applications (requirements for fire barriers):
1 - Subdivision of large uninterrupted cavities
To comply with Building Regulations - 30 minutes’
integrity plus 15 minutes insulation. The AIM Raised
Access Floor Fire Barrier meets and exceeds the
requirements of Approved Document Part B (in
England and Wales) as well as the fire safety sections
of other UK Building Regulations’.
2 - Alignment under a partition, to maintain partition rating
i) 30 minute partition - 30 minutes’ integrity plus 30 minutes’ insulation
ii) 60 minute partition - 60 minutes’ integrity plus 60 minutes’ insulation.
iii)120 minute partition - 120 minutes’ integrity plus 120 minutes’ insulation
3 - Reduce flanking transmission of sound
The AIM Raised Access Floor Barrier can be used to reduce flanking transmission of sound through the void it fills by at least 21 dB RW
4 - Plenum Applications
The AIM Raised Access Floor Barrier can also be used to help create a Plenum chamber under a raised access floor system.
PHYSICAL INFORMATION
- Length: 1000mm
- Widths: 75mm, 100mm & 125mm (depending on the fire rating required)
- Voids: 50 - 400mm (barrier to be compressed by 5%)
- Available cut to size and supplied with the required fixing clips
- Available in slab form for cutting on site as required
- Foil faced (see options)
- Also available Polythene sleeved
- Thermal Conductivity l = 0.036W/mK
FEATURES
- High density foil faced stone wool barrier
- Thicknesses to provide ½, 1 and 2 hour fire rating
- For use within voids up to 400mm
- Reduces airborne transmission of sound by a minimum of 21db Rw
- Solutions for power & communication cables
BENEFITS
- Prevents the passage of fire and smoke through underfloor cavities
- Reduces airborne sound through underfloor voids
- The product provides up to 120 minutes Integrity & Insulation when tested to BS EN 1366-4:2006+A1:2010
- Allows for power and communications to be run below the barrier
COMPONENTS AVAILABLE FROM AIM
Barrier
AIM Clip
Acrylic fire rated intumescent mastic (optional extra)
Foil tape for sealing joints (optional extra) Length - 45m Widths - 100mm, 125mm and 150mm
TECHNICAL INFORMATION
FIRE PERFORMANCE
Tested to BS EN 1366-4:2006+A1:2010.
Achieves the Euroclass rating of A1, non combustible.
The access floor and structural slab should have a proven fire rating at least equal to that of the barrier.
Fire Rating | Integrity | Insulation fire resistance | Barrier thickness | Maximum void |
---|---|---|---|---|
1/2 hour | 120 minutes | 30 minutes | 75mm | 400mm |
1 hour | 120 minutes | 60 minutes | 100mm | 400mm |
2 hour | 120 minutes | 120 minutes | 125mm | 400mm |
ACOUSTIC PERFORMANCE
AIM Raised Access Floor Barrier provides at least 21dB Rw sound reduction. The acoustic performance of the floor system must also be considered when assessing the room-to-room sound reduction figure.
Plenum Chambers
AIM Raised Access Floor Barrier may be used to create a plenum chamber however the effectiveness of the barrier is dependent on the quality of the installation. (or similar).
AS STANDARD
AIM Raised Access Floor Barrier is supplied pre-cut
in 1000mm lengths and three standard thicknesses
depending on the fire rating required. The product
supplied is as required to fill the void.
The pre-cut product is supplied with the required
fixing clips.
OPTIONS
The AIM Raised Access Floor Barrier is also available
in slab form for cutting on site as required. When
ordering in slab form the clips should be purchased
separately.
The product is also available fully foil enclosed for use
within plenum applications. It can also be suppled
polythene sleeved.
Foil tapes of 45m length and in widths of 100, 125
and 150mm for the optional sealing of joints.
TEST REPORTS
Test reports WF 432725 & WF 432729 cover the use
of AIM Raised Access Floor Fire Barrier in cavities up
to 400mm.
Tests are conducted to BS EN 1366-4:2006+A1:2010
and the principles of TR31.
INSTALLATION GUIDELINES
AIM Raised Access Floor Barrier is friction fitted into place in conjunction with fixing clips; it must fit tightly and completely fill the void with 5% compression.
AIM Raised Access Floor Barrier is friction fitted into place in conjunction with fixing clips; it must fit tightly and completely fill the void with 5% compression.
ITEMS REQUIRED FOR INSTALLATION
- PPE abrasion resistant gloves
- Drill
- PPE impact resistant goggles
- Screwdriver
- RPE dust mask
- Tape measure
- Insulation saw
STORAGE
Products are supplied on wooden pallets with edge
protection and a shower proof hood.
Products should be stored away from the elements until
ready for installation.
MAINTENANCE
This product does not contain moving parts and, if undisturbed in the underfloor cavity, requires no routine inspections or maintenance. It is recommended that the integrity of the barrier is rechecked if further works are carried out that may have involve disturbing the product e.g. installing new cables.
HEALTH & SAFETY
Insulation products supplied by AIM are considered to be
inert articles and as such are exempt from requirements to
provide a Safety Data Sheet.
A Product Safety and Handling Information Sheet is
available upon request.
ENVIRONMENT
Global warming potential = zero
AIM fire barrier products are manufactured from
stone wool insulation which is universally recognised
as being a sustainable and environmentally friendly
material.
Rockwool Stone Wool products may be recycled at
the end of their life by Rockwool Ltd.
Call 01656 868400 or email
[email protected] for further details.
ORDERING
To order this product the following information will be
required:
- Underfloor void Height
- Fire Performance Required
- Approximate Quantity
Products are typically supplied in four to five working
days but lead times may vary depending on existing
factory commitments.
There is no minimum order quantity or value although
small orders may attract transport surcharges.
TECHNICAL SUPPORT
Technical Support is available from our experienced sales team on 01293 582 400 or [email protected]
Our Partners & Affiliates
AIM are partners with NBS. Our products can be found on NBS Source and have been authored to NBS specification standards and have both CAWS and Uniclass 2015 classifications.
AIM are members of ASFP.
AIM are working in partership with Rockwool.
AIM are members of SRL.